Fire Alarm System

Blue Rays 10 Zone Fire Panel

Description:

10 Zone Micro Controller Based fire alarm panel. Supports 2 wire standard smoke detectors, Can attach speech dialer, Operating Voltage 24V, Individual zone indication, 3-7 digit user code, sturdy sheet metal cabinet with transparent cover and lock & key to prevent unauthorised access.

Main Features:

  • Supports 2 wire international standard smoke detectors.
  • Facility to attach speech dialer
  • Cabinet closed with a lock and key to restrict the access
  • Common tamper led for open or short in any zone
  • Panel can be programmed by a user code with user programmable 3-7 digit code
  • Panel can be armed or disarmed through code or a dedicated key
  • Any zone can be omitted
  • Manual call points can be operated even when some detectors have been removed
  • 12 event fire memory log with non-volatile memory
  • Sounders start automatically when fire is detected and can be programmed from 2 to 20 minutes
  • Single dedicated key to arm the panel and disarm the panel
  • Single dedicated key to manually start sounders and switch off the sounders
  • Single dedicated key for zone led test and for drill exercise
  • Two sounder outputs, each can switch 1 amp
  • Higher power sounders can be attached through an inbuilt relay
  • Battery space provided within the panel with plug in connectors

Bosch FPD7024 Fire Alarm Control Panels

Four initiating zones (expandable to eight); up to 20 two wire smoke detectors per zone, Programmable through front panel interface, remote FMR7033 Liquidcrystal Display (LCD) keypads, or remote programming software (RPS) through a DX4010V2 serial interface, Expandable for programming or reporting with Ethernet or cellular IP connectors (DX4020, ITS-DX4020-G, B420, B426, or B450/B44x), Two notification appliance circuits.

  • Current (alarm)*: 380 mA
  • Current (standby)*: 200 mA
  • Power (primary) : 120 VAC , 1.2 A maximum, 60 Hz or240 VAC , 0.75 A maximum, 50 Hz
  • * For product specific current values, see the product Installation Instructions.
  • Environment: Indoor, dry
  • Relative Humidity: Up to 95%, non-condensing
  • Temperature (operating): +32°F (0°C) to +120°F ( +49°C)
  • Color: Red
  • Dimensions (HxWxD): 20.8 in. x 15 in. x 4.3 in. (52.8 cm x 38.1 cm x 10.9 cm)
  • Material: Cold-rolled steelBase: 18 gauge (1.2 mm)Cover: 19 gauge (1.1 mm)
  • Current: 44 mA maximum per loop
  • Line resistance: 150
  • Voltage: 24 VDC nominal
  • NAC: 24 VDC nominal, 4 A maximum
  • On-board Relays: Three Form C contacts rated at 5 A, 28 VDC

Bosch D1255 Series VFD Key Pad

  • Easy to read vacuum fluorescent display (VFD)
  • Easy system control with menu keys
  • User controlled brightness and volume
  • Installer configured menus, text, and custom functions
  • Multiple or single area configurations

 

  • Connections: 4-wire flying lead for data and power
  • Resistance: 25 maximum
  • Temperature (Operating): 0C to +50C (+32F to +122F)
  • Relative Humidity: 5% to 85% at +30C (+86F)
  • Dimensions for D1255, D1255W, and D1255R: 11.7 cm x 21  cm x 2 cm (4.6 in. x 8.2 in. x 0.8 in.)
  • Dimensions for D1255B: 12.6 cm x 20 cm x 3.2 cm (5 in. x 7.9 in. x 1.3 in.)
  • Weight for All Models: 439 g (15.5 oz)
  • Material for All Models: CHI MEI POLYLAC PA757 ABS with UV Stabilizer. UL94-HB Fire Rated
  • Display Window: 16-character vacuum fluorescent displayEach character is a 14-segment unit
  • Indicators: Illuminated keysWarning and indicating tones
  • D1255 Series Keypad Models per Control Panel: Eight supervised 32 unsupervised
  • Voltage: Nominal 12 VDC
  • Current: Idle 104 mA, armed or disarmed;Maximum 206 mA, with keypad lit and warning tone on
  • POLYLAC is a registered trademark of CHI MEI Industrial Corporation, LTD.
  • Plexiglas is a registered trademark of Arkema.

D7030X LED Annunciators 

  • Use with the FPA˜1000 Analog Addressable Fire Panels or FPD˜7024 FACPs
  • LED indicates power and trouble conditions
  • LED annunciates eight individual zones expandable to 64 zones
  • Remote control panel reset and notification appliance silencing capabilities
  • Low profile, aesthetically appealing appearance
  • UL Listed

 

  • Environment: Indoor, dry
  • Dimensions (HxWxD):  4.5 in. x 6.5 in. x 1.5 in. (11.4 cm x 16.5 cm x 3.8 cm)
  • Current (alarm):  255 mA maximum (includes remote LED current). Use 190 mA for battery calculation.
  • Current (standby): 45 mA maximum (use 34 mA for battery calculation).
  • Voltage (operating):  12 VDC nominal